OJUS OL 125 D
PRODUCT ENQUIRY
Fill this form to get the best quote on our product range:
PRODUCT FEATURES
Power source
- OJUS LEYPOWER genets meet the latest CPCB II emission norms, are environment friendly and are designed to work under arduous conditions.
- The sturdy, 4 & 6 cylinder, in-line, water cooled four stroke Ashok Leyland range of diesel engines yield continuous power, enabling the generator to operate round the clock, withprime duty of 100% load.
- The inherent construction design of the engine ensure easy serviceability, accessibility and maintenance, even inside an acouslic enclosure.
- The standard scope of supply includes a power pack unit comprising of radiator mounted with standard control panel.
RTU (Ready-To-Use ) Genset
- Powered by Ashok Leyland engine coupled with single bearing brushless alternator
- Equipped with standard safety features like Low Lube Oil Pressure(LOP), High Water Temperature(HWT) and Emergency Stop.
- Choice of standard or AMF control panel.
- In built with fuel tank, residential silencer and battery.
Acoustic Enclosuers
- Manufactured with CNC machines for precision finish and high quality
- Powder coated with eco-friendly chemicals for long lasting weather- proofing
- Approved by CPCB
Genset Controller GC 1201
- Digitally controls the operation of the genset.
- Measures and displays parameters like Voltage, Frequency, Current, power Factor and Run Hours.
- Protects Genset by monitoring critical engines safety parameters.
- Supports Auto-Mains- Galore (AMF) function for single-phase and three-phase operation.
AMF control Panel
- Consists of a microprocessor based AMF control unit, which can operate on auto or manual mode. It monitors the engines safety parameters and alarm/trip conditions will be displayed on the front panel.
- Special alarm conditions include LLOP, HWT, overland, under/over speed, low fuel level. The controller comes with an inbuilt LVM and the parameters can be programmed to meet specific customer requirements.
- The display indication includes various conditions of operation which includes, Load on mains Load on DG , Mains Healthy DG On, auto and manual mode.
- The control panel consists of a multi-function meter which display AC current, Voltage, frequency, Power factor, Kilowatt Hour.
DG set model | Unit | OL 125D |
Power Rating | kVA | 125 |
Electric Power | kWe | 100 |
Rated Current | A | 173.9 |
No of Phase* | 3 -Phases/ 415V | |
DG Size (without Silencer) | l in mm | 3300 |
w in mm | 1250 | |
h in mm | 1565 | |
Fuel Tank Capacity | L | 175 |
System DC Voltage | V | 12 |
Battery | EXIDE GEN Plus/ AMCO OF SUITABLE CAPACITY | |
Weight (DG Set) | kg | 1874 |
Engine | ||
Engine Model | AL6DTIDG2 | |
Engine Rated HP | HP | 155.5 |
Aspiration | TA** | |
No of Cylinders/Configaration | 6/ In-Line | |
Bore X Stroke | mm | 104*113 |
Displacement | L | 5.76 |
Fuel Consumption @75% Load** | L/Hr | 21.6 |
Lube oil capacity approx | L | 17.5 |
Coolant capacity approx | L | 20 |
Governing Class | A0 | |
Governor | Electronic | |
Lube Oil Change Period | 600 Hours or 1 year whichever occurs earlier ( 10 to 160kVA)/ 250 Hours or 6 months whichever occurs earlier (250 kVA) | |
Lube oil specification | Gulf LEYPOWER XLL Diesel Engine Oil | |
ALTERNATOR | Brush-less, Single Bearing, IP23, Class H Insulated, 500Hz, Voltage Regulation of ± 1% |
Note: Power rating as per standard reference condition as per BS 5514/ ISO 3046/ ISO 8528.
Reference Condition: 27℃ ambient temp, 100 KPA (750 mm of HG) atmospheric condition and 60% humidity (as per ISO 10002, ISO 3046). The above specifications are liable to change due to continuous improvement and for reference only. OJUS Power & Technologies Private Limited reserves the right to revise the specification or dimension without prior notice.
*Single phase DG set is available optional from 5 kVA to 45 kVA
NA*: Naturally Aspirated.
TA**: Turbo-charged After-cooled.