OJUS POWER POWERED BY ASHOK LEYLAND, BAUDOUIN AND VOLVO - BEST DIESEL GENERATOR, INDIA | BEST DIESEL GENERATORS FROM 5KVA – 2250KVA
OJUS LP 400
PRODUCT ENQUIRY
Fill this form to get the best quote on our product range:
PRODUCT FEATURES
Power source
- ”OJUS” Packaged Baudouin Volvo powered DG sets meet the latest CPCB-II emission norms.
- Highly Fuel Efficient
- Best in class first load capability for 4000 series ratings
- Maximum deration tolerance
RTU (Ready-To-Use ) Genset
- Adhere to CPCB-II norms on noise(Wherever applicable).
- Residential silencer, suitable batteries with cable and in-built diesel tank (optional).
- Powered with Baudouin Volvo make engine coupled with single bearing brushless alternator of either LS or stamford
Acoustic Enclosuers
- The design and construction of the DG set ensure easy serviceability,accessibility and maintenance inside acoustic enclosure.
- The acoustic have been manufactured with specially procured CRCA sheet and using CNC machines for obtaining precision finish
AMF control Panel
- Compect
- Low operating cost
- Easy availability of spare parts
- Nation-wide serice network environment friendly
Leypower Genset Controller
- IP65 rating (with optional gasket)
- Control signal for auto transfer between mains(utility) and generator
- Hour counter provides accurate information for monitoring and maintenance
- User-friendly set-up and button layout for ease of use
- Fully configurable via the fascia or PC using USB communication
- Extremely efficient power save mode
- 3 phase generator sensing
- provision for 3 phase mains (utility) sensing
- provision for 3 phase generator current sensing
- provision for remote monitoring AND control through GPRS (optional)
- Provision for web monitoring (optional)
USP of Leypower Diesel generating sets
- Consists of a microprocessor based AMF Control unit,which can operate on auto as well as on manual mode.It monitors the engine safety parameters and alarm/trip conditions display on the front panel.
- Special alarm conditions include LLOP,HWT,overload,under/over speed,low fuel level. The controller comes with an inbuilt LVM and the parameters can be programmed to meet specific customer requirements.
- The specific indication includes various conditions of operation such as load on mains,Load on DG,main healthy,DG on,Auto and manual mode.
- The control panel consists of a multifunction mater which displays AC current/vottage,Frequency,Power factor,Kilowatt Hour.
- The generator set is also available with a standard control panel to operate in manual mode.
Specifications | Unit | LP 400 |
Power [email protected] PF, 415V, 50 Hz | kVA | 400 |
Electric Power | kWe | 320 |
Rated Current | Amp | 556 |
DG Size L | mm | 5800 |
W | 2000 | |
H (Including Base) | 2375 | |
DG Weight approx. | Kg | 4200 |
Fuel Tank Capacity | L | 700 |
Battery Capacity | AH | 150 |
System DC Voltage | V | 24 |
Engine Make | Baudouin Volvo | |
Engine Model | 2206D-E13TAG3 | |
Engine Nett Output Power | KW | 367 |
Engine Nett Output Power | HP | 493 |
Aspiration | TA | |
Rated Speed | RPM | 1500 |
No. of cylinders | 6 “In line” | |
Bore x Stroke | mm | 130×157 |
Displacement | L | 12.5 |
Compression ration | 16.3:1 | |
Fule Consumption @75% Load** | L | 68 |
Fuel Consumption @100% Load** | L | 87 |
Lube Oil System Capacity | L | 38 |
Lube Oil Grade | API CH 4 15W 40 | |
Governor/Class Class | Electronic/A0 | |
Coolant capacity | L | 52 |
Alternator Make | Leroy Somer | |
Alternator Model | LSA47.2 VS3 | |
Enclosure/Winding Insulation class | ||
Voltage Regulation | ± 1 % | |
Efficiency @75% Load | % | 94.4 |
Efficiency@100% Load | % | 93.8 |
Over Load Capacity | 10% over load for 1 Hour in every 12 Hours |
Note: The above DG ratings are “prime rating is as per standard referance condition as per BS 5514/ISO 3046/ISO 8528/ISO 10002,
Power rating- As per bs 5514/ISo 3046/ISO 8528 under standard referance conditions.
*open Dg set
**Specific gravity of fuel is considered for 850 gms/litre. +5% tolerance is applicable for the above consumption for the above consumption as per BS-5514/ISO-3046
Rating definition: continuous rating is defined as being the maximum power which the generating set is capable of delivering continuously whilst supplying a constant electrical load when operated for a unlimited number
Technical specifications are subject to change from time to time due to design improvements without notice. OJUS reserves the right to revise the specifications or dimensions without notice.