SpecificationUnitOL 100DLP320LP350LP380
Power RatingkVA100320350380
Electric PowerkWe80256280304
Rated CurrentA139.1445487529
DG Size (L×W×H)mm3300×1250×14005000×2000×28005000×2000×28005000×2000×2800
WeightKg1874470049005000
Fuel Tank CapacityL175990990990
System DC VoltageV12242424
Engine Model-AL6DTIDG1TAD1351GETAD1352GETAD1354GE
Engine Rated HPHP126.01379427446
Aspiration-TATATATA
DisplacementL5.7612.7812.7812.78
Fuel Consumption @75%L/hr17.54954.858.5
Fuel Consumption @100%L/hr-63.169.373.89
Lube Oil CapacityL17.5303030
Coolant CapacityL20242424
Efficiency @75% Load%-95.193.993.9
Efficiency @100% Load%-94.393.593.5



SpecificationLP415LP450LP500LP600LP650
Power Rating (kVA)415450500600650
Electric Power (kWe)332360400480520
Rated Current (A)577626695834904
Weight (Kg)57505900615063506650
Fuel Tank Capacity (L)990990990990990
System DC Voltage (V)2424242424
Engine ModelTAD1355GETAD1650GETAD1651GETWD1652GETWD1653GE
Engine Rated HP483528585687744
AspirationTATATATATA
Displacement (L)12.7816.1216.1216.1216.12
Fuel Consumption @75% (L/hr)64.7568.176.390.8103.56
Fuel Consumption @100% (L/hr)79.889.897.76120.8134.7
Lube Oil Capacity (L)3042424242
Coolant Capacity (L)2461617575
Efficiency @75% Load (%)94.994.994.994.694.6
Efficiency @100% Load (%)94.494.494.494.294.2
  • IP65 rating (with optional gasket)

  • Control signal for auto transfer between mains (utility) and generator

  • Hour counter provides accurate information for monitoring and maintenance periods

  • User-friendly set-up and button layout for ease of use

  • Fully configurable via the fascia or PC using USB communication

  • Extremely efficient power save mode

  • 3 Phase generator sensing

  • Provision for 3 phase mains (utility) sensing

  • Provision for 3 phase generator current sensing

  • Provision for Remote monitoring & control through GPRS (optional)

  • Provision for web monitoring (optional)

Some of the USP of Leypower Diesel generating sets are:

  • Compact

  • Low operating cost

  • Easy availability of spare parts

  • Nation-wide service network

  • Environment friendly

Power Source:

  • “Ashok Leyland” Packaged “VOLVO PENTA” powered DG sets meet the latest CPCB-II emission norms.

  • Highly Fuel Efficient

  • Best in class first step load capability.

  • Maximum deration tolerance

RTU (Ready to use) DG set unit

  • Adhere to CPCB-II norms on noise.

  • Residential silencer, suitable batteries with cable and in-built diesel tank (optional).

  • Powered with “VOLVO PENTA” make engine coupled with single bearing brushless alternator of either LS or Stamford

Acoustic Enclosures

  • The design and construction of the DG set ensure easy serviceability, accessibility and maintenance inside acoustic enclosure.

  • The acoustic have been manufactured with specially procured CRCA sheet and using CNC machine for obtaining precision finish.

AMF control panel (Optional)

  • Consists of a microprocessor based AMF Control unit, which can operate on auto as well as on manual mode. It monitors the engine safety parameters and alarm/trip conditions display on the front panel.

  • Special alarm conditions include LLOP, HWT, overload, under /over speed, low fuel level. The controller comes with an inbuilt LVM and the parameters can be programmed to meet specific customer requirements.

  • The specific indication includes various conditions of operation such as Load on Mains, Load on DG, Main Healthy, DG on, Auto & manual mode.

  • The control panel consists of a multifunction meter which displays AC current/Voltage, Frequency, Power factor, Kilowatt Hour.

  • The generator set is also available with a standard control panel to operate in manual mode.

Product Enquiry

Fill this form to get the best quote on our product range:

Hotline Number:
+91 974 000 7700
Enquire Now